Concrete mix pre-design

Reference quantities per cubic metre with the ACI 211.1 absolute volume method and the Meteoro Guayuriba aggregates: cement, water, gravel, sand, w/c ratio and f'cr. Every result is sealed with a folio and hash and can be verified. It does not replace the mix design: it needs trial batches and the responsible engineer's approval.

Mix data

Options

Left empty, 3.10 g/cm³ is used as an assumed value; confirm with your cement data sheet.

1,000 psi = 7 MPa, equivalence commonly used in Colombia (3,000 psi = 21 MPa).

Result

Example: 3,000 psi (21 MPa), slump 75-100 mm, 1" gravel

Concrete mix pre-design · PM-1243A3E7C2

21.0 MPa, slump 75-100 mm, 1" gravel: per m³, 350.9 kg cement, 193.0 kg water, 1067.7 kg gravel and 726.4 kg sand (SSD); w/c 0.550.

Quantities per m³ (aggregates in SSD condition)
ComponentPer m³Absolute volume
Cement350.9 kg0.1132 m³
Water193.0 kg0.1930 m³
Meteoro Guayuriba 1" gravel (SSD)1067.7 kg0.4058 m³
Meteoro Guayuriba alluvial sand (SSD)726.4 kg0.2730 m³
Entrapped air1.5 %0.0150 m³
Total2338.0 kg1.0000 m³
f'cr29.3 MPa
w/c ratio0.550
Proportion by weight (cement : sand : gravel)1 : 2.07 : 3.04
Theoretical unit weight2338.0 kg/m³
Cement in 50 kg bags7.02

Table values used

f'c from 21 to 35 MPa, no historical data: f'c + 8.3 MPa29.3 MPaACI 211.1
Mixing water, slump 75-100 mm, NMS 25 mm193 kg/m³ACI 211.1
Entrapped air, NMS 25 mm1.5 %ACI 211.1
w/c by linear interpolation between f'cr 30 MPa → 0.54 and 25 MPa → 0.610.550ACI 211.1
b/b0, NMS 25 mm, fineness modulus 2.96: interpolation between 2.80 → 0.67 and 3.00 → 0.650.654ACI 211.1
Cement density3.10 g/cm³ (assumed value, confirm with your cement data sheet)Assumed value
Dry-rodded gravel (b/b0 × unit weight)1060.8 kgACI 211.1

Data sheet values used

Campaign: September 2026 characterization

Meteoro Guayuriba 1" gravel
NMS 25 mm · Relative density SSD 2,631 (INV E-223) · Absorption 0,65 % (INV E-223) · Compacted unit weight 1,622 kg/dm³ (NTC 92 · INV E-217)
Meteoro Guayuriba alluvial sand
Relative density SSD 2,661 (INV E-222) · Absorption 0,9 % (INV E-222) · Fineness modulus 2,96

Traceability

Folio
PM-1243A3E7C2
Inputs
f'c 21.0 MPa; slump 75-100 mm; gravel 1"; cement density 3.10 g/cm³ (assumed value, confirm with your cement data sheet)
Engine
meteoro-prediseno-aci211-1.0.0
SHA-256 hash
1243a3e7c28de6dc71d7041199175e346ea962efd5fadfcf0c5cf10dd1ff86d5

Reference pre-design calculated with the ACI 211.1 method and the September 2026 characterization of the Meteoro Guayuriba aggregates. It does not replace the mix design: it requires laboratory trial batches, moisture adjustment and approval by the responsible engineer (NSR-10).

How it is computed

  1. Required strength f'cr. Without historical deviation data: f'c below 21 MPa, f'cr = f'c + 7.0 MPa; 21 to 35 MPa, f'cr = f'c + 8.3 MPa. Above 40 MPa f'cr, an advisor reviews it.
  2. Water and air. Mixing water comes from the table by slump and nominal maximum size of the gravel; entrapped air from the table by nominal maximum size.
  3. w/c ratio and cement. The w/c ratio is interpolated between the table values for f'cr; cement is water divided by the w/c ratio.
  4. Gravel. The dry-rodded gravel volume per m³ (b/b0) is interpolated for the sand fineness modulus (2.96) and multiplied by the compacted unit weight from the data sheet, then converted to SSD with the absorption.
  5. Sand by absolute volume. Sand completes the cubic metre: 1 m³ minus the absolute volumes of water, cement, gravel and air, times the SSD density of the sand.
  6. Moisture and folio. With the site moisture of the aggregates, water and wet weights are corrected. Every result is sealed with a SHA-256 hash of inputs and outputs and a folio anyone can verify.

ACI 211.1 tables used

Mixing water (kg/m³), non-air-entrained concrete
SlumpNMS 12.5 mmNMS 25 mm
25-50 mm199179
75-100 mm216193
150-175 mm228202
Entrapped air2.5 %1.5 %
w/c ratio by f'cr, non-air-entrained concrete (linear interpolation)
f'cr (MPa)w/c
400.42
350.47
300.54
250.61
200.69
150.79
Dry-rodded gravel volume per m³ (b/b0)
Fineness modulusNMS 12.5 mmNMS 25 mm
2.400.590.71
2.600.570.69
2.800.550.67
3.000.530.65

Table source: ACI 211.1.

Aggregate data sheets

September 2026 characterization values used by the engine: SSD relative density, absorption and compacted unit weight of each gravel; SSD relative density, absorption and fineness modulus of the sand.

Scope

  • Non-air-entrained concrete without admixtures.
  • f'c from 17 to 35 MPa (f'cr up to 40 MPa).
  • Slump of 25-50, 75-100 or 150-175 mm.
  • Meteoro Guayuriba 1" (25 mm) or 1/2" (12.5 mm) gravel and Meteoro Guayuriba alluvial sand.
  • Air-entrained concrete, admixtures, asphalt mixes, granular blends and higher f'c: an advisor reviews it.

Verification

Enter a folio to recompute it with the same engine and the same data sheet values.